Annual Fire Pump Testing

Required every year under LAFD Reg 4.

LAFD Regulation 4 lists fire pumps as a one-year test, so building fire pumps in the City of Los Angeles must be tested every year by an LAFD-certified tester. We run the annual test to NFPA 25 and LAFD’s Reg 4 test procedure, then file the results with LAFD through The Compliance Engine within 7 days.

​

Why the annual test matters.

In a high-rise, or anywhere city water pressure isn’t enough, the fire pump is what pushes water to the sprinklers and standpipes on the upper floors. A pump can start fine and still fall short under flow, which is why the annual test flows water.

​

What the flow test measures.

We run the pump at churn (no flow), then at 50%, 100% and 150% of its rated flow, recording suction and discharge pressure, RPM and flow at each point. At 150% the pump must still produce at least 65% of its rated pressure, and on a city-fed pump the suction pressure shouldn’t drop below 20 psi. We compare the readings with the pump’s factory curve and earlier tests.

​

Electric and diesel pumps.

We test electric and diesel fire pumps and their controllers, including automatic and manual starts, alarm signals at the fire alarm panel, and on diesels the batteries, fuel and cooling system. We fix what fails, and your report includes photos of every deficiency.

Fire Pump Services

What We Test & Repair

Annual fire pump flow test

Churn plus 50%, 100% and 150% of rated flow, compared with the pump’s factory curve and filed with LAFD within 7 days.

​

No-flow (churn) runs

Between annual tests, NFPA 25 calls for no-flow runs: weekly for at least 30 minutes on diesel pumps, and monthly for at least 10 minutes on most electric pumps (weekly in some buildings, such as high-rises beyond fire department pumping capacity).

​

Electric fire pumps

Automatic and manual start tests, voltage and amperage readings, transfer to backup power where a transfer switch is installed, and pump running and trouble signals at the fire alarm panel.

​

Diesel fire pumps

Batteries and chargers, fuel level and condition, cooling water flow, oil pressure and engine speed, checked while the engine runs.

​

Fire pump repairs

Controllers, packing leaks, gauges, relief valves, jockey pumps and other deficiencies repaired and retested. LAFD requires corrections within 30 days of the initial test.

​

Emergency fire pump service

Same-day calls are usually possible in the San Fernando Valley and central LA.

​

Intervals follow LAFD’s Chief’s Regulation 4 schedule and NFPA 25.

Pumps, pipes, valves, and control panels. Part of a fire suppression system. The setup is well-organized, with the pipes carefully connected to the pumps and valves.
New fire sprinkler control valve after repair in a Los Angeles building
Corroded fire sprinkler control valve flagged as a deficiency in Los Angeles
Emergency fire sprinkler valve repair in Los Angeles
SERVICES
Standpipe hose valve and PRV testing in Los Angeles
Fire sprinkler riser during Reg 4 testing in Los Angeles
Fire sprinkler head replacement in Los Angeles
a fire protection system setup featuring black pipes with red fittings and control valves. It includes pressure gauges, red valves, labeled warning signs, and electrical components, indicating integration with monitoring systems.

How It Works

From notice to filed results in three steps.

​

1. Schedule

Call or send the quote form with the system and due date. We offer same-week appointments and plan the details with tenants or management: where the flow-test water goes, who watches the fire alarm panel, and access to the pump room and test header.

​

2. Test and repair

LAFD-certified testers perform the full flow test on site. If something fails, we quote the repair on the spot and can often fix it the same visit.

​

3. We file with LAFD

We file your results with LAFD through The Compliance Engine within 7 days and send you copies for your records.

Fire Pump Questions, Answered

How often does a fire pump need testing in Los Angeles?

Every year. LAFD Regulation 4 lists fire pumps as a one-year test, performed by an LAFD-certified tester. NFPA 25 also calls for no-flow runs between annual tests: weekly for diesel pumps and monthly for most electric pumps.

​

What happens during the annual fire pump test?

We run the pump at churn and at 50%, 100% and 150% of its rated flow, record suction and discharge pressures and RPM, check the controller and alarm signals, and compare the results with the pump’s factory curve. At 150% flow the pump must still make at least 65% of its rated pressure.

​

What’s the difference between a churn test and a flow test?

A churn test runs the pump with no water flowing to confirm it starts, runs smoothly and holds shutoff pressure. A flow test measures what the pump actually delivers at rated and peak flow. A churn test alone says little about real capacity, so the annual test includes both.

​

Does a fire pump test discharge water?

Usually, yes. The water goes out through a test header and hose streams or to a drain that can take full flow, unless the system has a flow meter loop that recirculates it. We plan the discharge path before test day.

​

Why do fire pumps fail the annual test?

Common causes include weak diesel batteries, old or contaminated fuel, a controller left in manual or showing a fault, partly closed suction or discharge valves, a jockey pump covering for a slow leak, and a missing factory curve or prior test to compare against.

​

What if my fire pump fails the test?

LAFD requires defects to be corrected within 30 days of the initial test, then the pump is retested. We quote repairs on the spot and can often fix them the same visit.

​

Do you test diesel fire pumps?

Yes. We test electric and diesel fire pumps and their controllers. On diesel pumps we also check the batteries, fuel and cooling system, the usual reasons an engine won’t start when it’s needed.

​

Our pump controller shows a fault. Can you repair it?

Yes. We repair electric and diesel fire pumps and replace pump, controller and valve components. Same-day calls are usually possible in the San Fernando Valley and central LA; call (818) 739-9849.

​

How much does fire pump testing cost?

It depends on the pump and the building. We quote per building, usually within one business day.

​

Do you file the results with LAFD?

Yes. Our certified tester files the results through The Compliance Engine within 7 days of the test, as Reg 4 requires. Filing is included, and your report includes photos of any deficiencies.

​

What areas do you serve?

The San Fernando Valley, central Los Angeles, the Westside and South Bay, and the Paramount and Long Beach area.

 A formal letter from the Los Angeles Fire Department (LAFD). Regulation 4 testing , testing renewal notice
two elevators with sleek stainless steel doors and wooden interiors, adding a touch of elegance to the building. The floor outside the elevators features tiles with a wood-like pattern that complements the overall aesthetic.
side of a brick building equipped with three metal fire escape platforms. These platforms are stacked vertically, each connected by a ladder, forming a clear escape route.
Industrial generator installed outdoors, near a peach-colored building wall. The generator itself is encased in a white and black shell, with ventilation panels and a small window on one side
A fire safety setup featuring a fire hose reel housed in a glass cabinet, a red fire alarm button centrally located for emergencies, and a red fire exit door marked with "FIRE EXIT" in white text, equipped with a push bar for quick access during evacuations.

Get a Quote

 

Thanks for submitting!

pump-room.BSHsSXsW_2as7JE.webp

Head Office

Employment

15758 Vintage Street

North Hills, CA 91343

(818) 739-9849

To apply for a job at Ace Fire Protection,

please send a message using the contact form above with the subject "employment"

  • LinkedIn
  • Facebook
  • Instagram
  • Yelp!
  • Youtube

© 2022 by ACE FIRE LA. Terms Privacy policy.  Created by Free Mind Graphics

bottom of page