Annual Fire Pump Testing
Required every year under LAFD Reg 4.
LAFD Regulation 4 lists fire pumps as a one-year test, so building fire pumps in the City of Los Angeles must be tested every year by an LAFD-certified tester. We run the annual test to NFPA 25 and LAFD’s Reg 4 test procedure, then file the results with LAFD through The Compliance Engine within 7 days.
​
Why the annual test matters.
In a high-rise, or anywhere city water pressure isn’t enough, the fire pump is what pushes water to the sprinklers and standpipes on the upper floors. A pump can start fine and still fall short under flow, which is why the annual test flows water.
​
What the flow test measures.
We run the pump at churn (no flow), then at 50%, 100% and 150% of its rated flow, recording suction and discharge pressure, RPM and flow at each point. At 150% the pump must still produce at least 65% of its rated pressure, and on a city-fed pump the suction pressure shouldn’t drop below 20 psi. We compare the readings with the pump’s factory curve and earlier tests.
​
Electric and diesel pumps.
We test electric and diesel fire pumps and their controllers, including automatic and manual starts, alarm signals at the fire alarm panel, and on diesels the batteries, fuel and cooling system. We fix what fails, and your report includes photos of every deficiency.
Fire Pump Services
What We Test & Repair
Annual fire pump flow test
Churn plus 50%, 100% and 150% of rated flow, compared with the pump’s factory curve and filed with LAFD within 7 days.
​
No-flow (churn) runs
Between annual tests, NFPA 25 calls for no-flow runs: weekly for at least 30 minutes on diesel pumps, and monthly for at least 10 minutes on most electric pumps (weekly in some buildings, such as high-rises beyond fire department pumping capacity).
​
Electric fire pumps
Automatic and manual start tests, voltage and amperage readings, transfer to backup power where a transfer switch is installed, and pump running and trouble signals at the fire alarm panel.
​
Diesel fire pumps
Batteries and chargers, fuel level and condition, cooling water flow, oil pressure and engine speed, checked while the engine runs.
​
Fire pump repairs
Controllers, packing leaks, gauges, relief valves, jockey pumps and other deficiencies repaired and retested. LAFD requires corrections within 30 days of the initial test.
​
Emergency fire pump service
Same-day calls are usually possible in the San Fernando Valley and central LA.
​
Intervals follow LAFD’s Chief’s Regulation 4 schedule and NFPA 25.








How It Works
From notice to filed results in three steps.
​
1. Schedule
Call or send the quote form with the system and due date. We offer same-week appointments and plan the details with tenants or management: where the flow-test water goes, who watches the fire alarm panel, and access to the pump room and test header.
​
2. Test and repair
LAFD-certified testers perform the full flow test on site. If something fails, we quote the repair on the spot and can often fix it the same visit.
​
3. We file with LAFD
We file your results with LAFD through The Compliance Engine within 7 days and send you copies for your records.
Fire Pump Questions, Answered
How often does a fire pump need testing in Los Angeles?
Every year. LAFD Regulation 4 lists fire pumps as a one-year test, performed by an LAFD-certified tester. NFPA 25 also calls for no-flow runs between annual tests: weekly for diesel pumps and monthly for most electric pumps.
​
What happens during the annual fire pump test?
We run the pump at churn and at 50%, 100% and 150% of its rated flow, record suction and discharge pressures and RPM, check the controller and alarm signals, and compare the results with the pump’s factory curve. At 150% flow the pump must still make at least 65% of its rated pressure.
​
What’s the difference between a churn test and a flow test?
A churn test runs the pump with no water flowing to confirm it starts, runs smoothly and holds shutoff pressure. A flow test measures what the pump actually delivers at rated and peak flow. A churn test alone says little about real capacity, so the annual test includes both.
​
Does a fire pump test discharge water?
Usually, yes. The water goes out through a test header and hose streams or to a drain that can take full flow, unless the system has a flow meter loop that recirculates it. We plan the discharge path before test day.
​
Why do fire pumps fail the annual test?
Common causes include weak diesel batteries, old or contaminated fuel, a controller left in manual or showing a fault, partly closed suction or discharge valves, a jockey pump covering for a slow leak, and a missing factory curve or prior test to compare against.
​
What if my fire pump fails the test?
LAFD requires defects to be corrected within 30 days of the initial test, then the pump is retested. We quote repairs on the spot and can often fix them the same visit.
​
Do you test diesel fire pumps?
Yes. We test electric and diesel fire pumps and their controllers. On diesel pumps we also check the batteries, fuel and cooling system, the usual reasons an engine won’t start when it’s needed.
​
Our pump controller shows a fault. Can you repair it?
Yes. We repair electric and diesel fire pumps and replace pump, controller and valve components. Same-day calls are usually possible in the San Fernando Valley and central LA; call (818) 739-9849.
​
How much does fire pump testing cost?
It depends on the pump and the building. We quote per building, usually within one business day.
​
Do you file the results with LAFD?
Yes. Our certified tester files the results through The Compliance Engine within 7 days of the test, as Reg 4 requires. Filing is included, and your report includes photos of any deficiencies.
​
What areas do you serve?
The San Fernando Valley, central Los Angeles, the Westside and South Bay, and the Paramount and Long Beach area.





Get a Quote