Case Study: 13 Sprinkler Heads Replaced in One Visit at a Van Nuys Adult Day Health Care Center
An annual sprinkler test at an adult day health care center in Van Nuys found 10 problems. We corrected all of them in one visit of about 4 hours, and the retest passed the same day.
The building
An adult day health care center in Van Nuys, Los Angeles.
What we found
Outdated, painted or crusted sprinkler heads in the kitchen, a restroom, the nursing area, a storage room and outside.
The inspector’s test valve was not connected to the main.
The control-valve sign and the drain sign were missing.




What we fixed
In one visit of about 4 hours we replaced 13 sprinkler heads, connected the inspector’s test valve and installed both signs.

The result
The retest passed the same day.
Why it matters
The inspector’s test valve is how a tester confirms that flowing water sets off the alarm, so a valve that is not connected means that check cannot be done. Valve signs tell staff and firefighters which valve controls what.